8644 WAGO I/O
System 750
p. 2/19
Specications Pilot valve type
0460, 6524, 6525 0461, 6526, 6527
Fieldbus type
PROFIBUS DP, INTERBUS, DeviceNet,
CANopen, Ethernet, others on request
PROFIBUS DP, INTERBUS, DeviceNet,
CANopen, Ethernet, others on request
Electrical modules
WAGO I/O System 750 WAGO I/O System 750
Digital modules
2 or 4 inputs
2 or 4 outputs, others on request
2 or 4 inputs
2 or 4 outputs, others on request
Analog modules
2 or 4 inputs (0-10 V, 0-20 mA, 4-20 mA, RTD, TC)
2 outputs (0-10 V, 0-20 mA, 4-20 mA) others on
request
2 or 4 inputs (0-10 V, 0-20 mA, 4-20 mA, RTD, TC)
2 outputs (0-10 V, 0-20 mA, 4-20 mA) others on
request
Operating voltage
24 V/DC 24 V/DC
Permissible voltage tolerance
+20%/-15% (by use of Type 0460: ±10%) +20%/-15% (by use of Type 0461: ±10%)
Residual ripple
1 Vss 1 Vss
Rated power per valve
1 W (0.5 W nominal power after 120 ms) 2 W (1 W nominal power after 120 ms)
Rated current per valve
43 mA (28 mA holding current after 120 ms) 86 mA (56 mA holding current after 120 ms)
Temperatures
Operating 32°F to 131°F (0°C to +55°C)
(by use of Type 0460: 32°F to 122°F (0°C to +50°C))
32°F to 131°F (0°C to +55°C)
(by use of Type 0461: 32°F to 122°F (0°C to +50°C))
Storage -4°F to 140°F (-20°C to +60°C) -4°F to 140°F (-20°C to +60°C)
Rating
IP20
IP65 in closed eld housing
IP20
IP65 in closed eld housing
Approvals for hazardous areas
Zone 2 on request
Application example