WAGO Modular IO System INTERBUS S Manual de servicio Pagina 44

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 161
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 43
Counter Module 750-404 6
:$*2,26<67(0
Peak Time Counter 750-404/000-002
Technical data
The counter module also can be ordered as peak time counter with 750-404/000-002.
This description is only intended for hardware version X X X X 0 0 0 1- - - -. The
serial number can be found on the right side of the module.
The counter begins processing with pulses at the CLOCK input. The changes from 0 V
to 24 V are counted.
The counter counts up if the input U/D is set at 24 V. With an open circuit input or 0 V
the counter counts backwards.
The two bottom contacts each include another output. These outputs are activated
through bits in the control byte.
The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers
(except for the economy type).