Vista de pagina 68
Analog Inputs 750-452, 454,482,484
:$*2Ç,2 Ç6<67(0
5
Input current
0-20 mA
Binary value X : without meaning
F : short circuit
open circuit
Ü : overflow
X F Ü
Hex. Dec.
> 20 0100 0000 0000 0 0 0 1 40 01 16385
20 0100 0000 0000 0 0 0 0 40 00 16384
10 0010 0000 0000 0 0 0 0 20 00 8192
5 0001 0000 0000 0 0 0 0 10 00 4096
2.5 0000 1000 0000 0 0 0 0 08 00 2048
1.25 0000 0100 0000 0 0 0 0 04 00 1024
0.625 0000 0010 0000 0 0 0 0 02 00 512
0.0976 0000 0000 0000 1 0 0 0 00 08 8
0 0000 0000 0000 0 0 0 0 00 00 0